A home battery sample order should be defined before the unit ships. This checklist helps a distributor confirm the model, quantity, test scope, documents, logistics and responsibilities that must be agreed before ordering.
Before the sample is ordered, confirm what the supplier will send, which inverter and load conditions will be tested, which documents are required, how freight and sample cost are handled, and how a successful sample will lead to a repeatable production version.
The acceptance test belongs to the receiving stage. The order-stage decision is different: “Have we defined the exact sample and commercial conditions well enough to make the test meaningful?”
What to confirm before placing the sample order
A sample is a single physical unit. The first PO is a supply commitment. The second decision needs more evidence than the first one.
| Stage | Main question | Evidence to keep |
|---|---|---|
| Sample test | Does the unit match the quotation and operate normally? | Photos, readings, test conditions and fault records |
| System check | Does it work with the selected inverter and installation plan? | Model-level compatibility record and commissioning notes |
| First-PO review | Can the supplier repeat the same configuration? | Approved sample sheet, document revisions and PO clauses |
This distinction prevents a common purchasing mistake. A battery can work on a bench and still fail to communicate with the inverter that the distributor plans to sell. A unit can also pass a test while its label, firmware, accessories or manual belong to another version.
The sample acceptance record should close these gaps before the PO is released.
Set the sample scope before the order is placed
Do not order a sample with only a capacity number. Give the supplier the system conditions that the sample must meet.
Record:
- target country and application;
- home backup, solar self-consumption, weak-grid or off-grid use;
- required battery capacity and voltage platform;
- target inverter brand, model and firmware where available;
- CAN or RS485 requirement;
- expected parallel quantity;
- sample quantity and first-PO quantity;
- private-label, packaging and document requirements;
- required test records and warranty documents.
Sample order information sheet
| Field | What to write down |
|---|---|
| Battery model | Exact model code, suffix and revision |
| Nominal energy | kWh and Ah where applicable |
| Nominal voltage | V |
| Charge/discharge current | Recommended and maximum values |
| Target inverter | Brand, exact model and firmware |
| Communication | CAN, RS485 or another specified protocol |
| Installation | Wall-mounted, floor-standing, rack, all-in-one or parallel system |
| Required documents | Datasheet, manual, protocol sheet, compatibility list and warranty |
| Acceptance result | Pass, conditional approval or hold |
The acceptance sheet should travel with the sample. It becomes the reference for the first PO.
Check the package, label and battery identity first
Start with the carton and the product label. Do not begin with the mobile app.
Photograph and record:
- water marks, crushing, punctures or broken straps on the outer package;
- model and serial number on the carton;
- transport and handling marks;
- enclosure cracks, deformation or loose panels;
- terminals, covers, switches and displays;
- mounting hardware and communication cables;
- manuals, warranty cards and other promised accessories.
Then compare the product with the quotation and datasheet.
| Item | Record | Why it matters |
|---|---|---|
| Model | Exact model code and suffix | Similar names can represent different voltage or enclosure versions |
| Chemistry | LiFePO4, NMC or the specified chemistry | Chemistry affects voltage, charging limits and documents |
| Nominal voltage | Value on the label and datasheet | The inverter must match the battery operating range |
| Rated capacity | Ah and nominal kWh | Capacity does not prove usable energy or power capability |
| Production date | Month, year and batch | Old stock may have a different firmware or support status |
| Cell and BMS version | Model and firmware where available | Version changes can affect communication and expansion |
| Serial number | Photo and written record | Needed for traceability and warranty claims |
Do not accept a mismatch as a minor paperwork issue. If the label says one model and the manual describes another, stop the technical test until the supplier explains which version was delivered.
Use one real model to read the numbers correctly

A datasheet example helps the buyer see how the numbers connect.
CVC’s M16S314BL-YV home battery is listed at 51.2 V nominal voltage and 314 Ah rated capacity. The nominal energy calculation is:
51.2 V × 314 Ah = 16.0768 kWh
The listed nominal energy is about 16.076 kWh after rounding. That calculation checks the relationship between voltage, capacity and nominal energy. It does not prove that the battery will deliver the full figure in a field installation.
For the sample, the distributor should still record:
- the starting SOC;
- the charge and discharge current;
- the cut-off voltage or SOC;
- the ambient and battery temperature;
- the test duration;
- the measured energy delivered;
- the BMS limits during the test.
Use the M16S314BL-YV 16kWh LiFePO4 home battery as a model reference, then use the current datasheet and manual for the exact sample under review.
Run a controlled charge-discharge test

The first electrical test should answer one question: does the sample behave within its documented operating range under a recorded condition?
Write down the test conditions before starting.
| Test item | Record these conditions |
|---|---|
| Starting SOC | SOC before charging or discharging |
| Charging source | Inverter, charger or test equipment |
| Charge current | Set current and measured current |
| Discharge load | Load type and power |
| Test duration | Start and end time |
| Battery voltage | Before, during and after the test |
| Temperature | Ambient and battery temperature |
| Alarm status | Code, time and recovery action |
| End condition | Cut-off, low SOC, manual stop or fault |
Use this sequence:
- Power on the battery and record voltage, SOC and temperature.
- Start charging at the supplier’s recommended setting.
- Check whether the current remains within the expected range.
- Run a controlled discharge with a known load.
- Record voltage, current, temperature and SOC at defined intervals.
- Check for alarms, unusual heat, smell, noise or abnormal power limitation.
- Repeat the start-up and communication check after the test.
Do not call a short discharge a capacity test. A capacity result needs a defined current, start SOC, end voltage, temperature and test instrument. If the project requires a formal capacity report, ask the supplier or an independent laboratory for a report with those conditions.
The same rule applies to cycle-life claims. A cycle number has meaning only when the charge rate, discharge rate, temperature, depth of discharge and end-of-life threshold are known.
Check BMS protection and alarm behavior

The distributor does not need to create dangerous faults to approve a sample. The job is to confirm that the normal limits, alarms and service instructions are visible and documented.
Check:
- SOC and cell data visibility;
- over-temperature and low-temperature behavior;
- over-current and low-voltage alarms;
- whether the inverter receives the alarm;
- alarm code descriptions in the manual;
- documented recovery procedure;
- warranty treatment after a protection event;
- supplier contact for technical support.
If the sample shows swelling, leakage, abnormal heat, smoke, a damaged terminal or repeated unexplained protection, stop the test. Isolate the unit according to the supplier’s safety instructions and contact professional after-sales support.
Do not open the enclosure, replace the BMS or force a wake-up with another battery. Internal cell and BMS work belongs to the supplier or a qualified service team.
Verify communication with the target inverter

A CAN or RS485 port does not prove compatibility. The sample must communicate with the exact inverter model that the distributor plans to sell or install.
Check communication in four layers:
| Layer | What to verify |
|---|---|
| Electrical | Voltage range, charge limit, discharge limit and current capability |
| Physical interface | CAN, RS485, RS232, connector and cable |
| Network settings | Pinout, baud rate, address, termination and parallel settings |
| Application protocol | SOC, alarms, charge limits, discharge limits and firmware support |
Request these documents before approving the sample:
- BMS communication protocol sheet;
- CAN or RS485 pinout;
- baud rate and address settings;
- approved inverter list;
- required inverter firmware;
- battery firmware version;
- parallel communication instructions;
- wake-up and sleep procedures;
- fault-code and recovery instructions.
Then test the complete battery-inverter combination.
The record should show:
- whether the inverter identifies the battery;
- whether SOC remains stable;
- whether charge and discharge limits are read correctly;
- whether charging and discharging respond to the BMS;
- whether alarms reach the inverter;
- whether communication returns after a restart.
| Communication result | PO status |
|---|---|
| The battery has a CAN or RS485 port | Do not approve yet |
| The inverter receives some battery data | Continue testing |
| The inverter identifies the model and SOC | Check limits and alarms |
| Model, SOC, limits, alarms and restart recovery all work | Communication test passes |
For the wider voltage, protocol and firmware check, see the battery and inverter compatibility checklist and the CAN/RS485 communication checklist.
Check the documents, packaging and after-sales path

A sample can pass technically and still be a poor first-order choice if the supplier cannot support installation and service.
The document pack should include:
- product datasheet;
- installation manual;
- quick-start guide;
- wiring diagram;
- CAN/RS485 communication document;
- approved inverter list;
- fault-code list;
- warranty terms;
- certification and test documents;
- transport files;
- accessory list;
- spare-parts information.
Check each document against the exact model and revision. A certificate for a similar enclosure, a manual for an older BMS or a compatibility list without the battery suffix does not close the file.
Before the first PO, confirm:
- sample and batch products will use the same cell and BMS configuration;
- the factory can provide end-of-line test records;
- serial numbers and production batches are traceable;
- packaging and accessories will match the approved sample;
- product changes require written notification;
- the warranty identifies the responsible party;
- the supplier has a procedure for faults, replacements and spare parts.
The home battery supplier document pack gives the buyer a separate file-by-file review route.
Confirm expansion and version control
“Expandable” needs a model-level answer.
Ask the supplier:
- Which model can be added later?
- Must all modules use the same model and production batch?
- Must BMS firmware match?
- Is there an age limit between modules?
- Can the inverter handle the additional current and capacity?
- Is the system expanded in parallel, series or another architecture?
- Does the warranty cover the expanded system?
- What happens if the original module is discontinued?
Record the answer in the sample approval sheet. Do not leave “supports expansion” as a single brochure line.
Turn the sample result into a first-PO decision
Use three results.
Approved for first PO discussion
Use this result when:
- the model and chemistry match the quotation;
- the label, serial number and documents match;
- basic charging and discharging work as expected;
- the target inverter recognizes the battery;
- SOC, alarms and charge/discharge limits are visible;
- packaging and accessories are complete;
- the expansion path is documented;
- the production version is locked.
Conditional approval
Use this result when the sample operates, but one or more commercial or technical items remain open. Typical examples are a missing protocol sheet, incomplete packaging, unclear alarm recovery or unconfirmed firmware.
Write the supplier actions, owner and deadline into the record. Do not release the PO from a verbal promise.
Hold or reject
Hold or reject the sample when:
- the chemistry, model or key electrical parameters differ from the quotation;
- the battery shows unexplained protection behavior;
- the target inverter cannot communicate with the battery;
- the enclosure or terminals are damaged;
- safety-related damage is visible;
- required installation and service documents are unavailable;
- the supplier cannot confirm the batch configuration.
Add the approved sample to the purchase order
The sample test has commercial value only when the result becomes part of the order record.
The first PO should identify:
- product model and revision;
- cell and BMS configuration;
- firmware and communication protocol;
- target inverter model;
- nominal voltage, capacity and current limits;
- packaging and label version;
- accessory list;
- documents supplied with the order;
- factory test requirements;
- warranty terms;
- spare parts and after-sales path;
- product change notification procedure;
- sample-to-batch consistency requirement.
Attach the signed sample approval sheet, final datasheet, installation manual, warranty, communication document, packaging record and accessory list.
Keep responsibilities clear
A distributor can complete the receiving and document review. An installer or engineer should complete system commissioning. Internal cell and BMS work belongs to the supplier or a qualified service team.
| Responsible party | Suitable checks |
|---|---|
| Distributor | Model, label, packaging, accessories, manuals, basic readings and test records |
| Installer or engineer | Power wiring, inverter settings, CAN/RS485 communication, parallel setup and commissioning |
| Supplier or qualified service team | Internal BMS faults, damaged cells, insulation faults, protection-board replacement and abnormal heat |
This division keeps the sample process useful without turning a receiving inspection into an unsafe repair job.
Sample acceptance record
Use one record for every sample. Include:
- supplier and factory;
- battery model and serial number;
- production date and batch;
- chemistry, voltage and capacity;
- cell and BMS information;
- target inverter and firmware;
- communication protocol;
- test date and operator;
- charging and discharging results;
- alarm records;
- packaging and accessory check;
- document revisions;
- expansion confirmation;
- supplier corrective actions;
- final result: approved, conditional approval or hold.
A sample is ready for a first PO when this record is complete. Turning the unit on is only the first check.
Frequently asked questions
Can I place a bulk order if the sample charges and discharges normally?
No. Add the model, document, communication, alarm, packaging and production-version checks before releasing the PO.
Does a CAN port prove that the battery is compatible with the inverter?
No. Confirm the pinout, protocol, baud rate, firmware, inverter model and operating limits. Then test the complete combination.
Does a distributor need to perform a full capacity test?
A distributor can record a controlled functional test. A formal capacity result needs defined current, voltage, temperature, end point and test equipment. Request a supplier or third-party report when the project requires one.
Can I open the battery if the sample shows an alarm?
No. Stop the test and contact the supplier or qualified service team. Internal BMS and cell work is not a distributor receiving check.
What should be attached to the first purchase order?
Attach the approved sample record, final datasheet, manual, warranty, communication document, packaging and accessory list, and any agreed certification or transport files.
Need help checking a home battery sample?
CVC can help distributors organize sample information, match the battery with the intended inverter, request communication and testing documents, and coordinate supplier corrections before the first purchase order.
Send CVC the target country, battery model or required capacity, planned order quantity, inverter brand and model, sample photos or test records, missing documents and expected purchase date.
Use these checks before requesting a sample: Sample Approval Checklist · BMS and Inverter Communication Requirements · OEM/ODM support
Need help checking a home battery sample?
Tell us the target country, battery model, planned quantity and inverter setup. CVC can help organize sample checks and supplier follow-up.